Scroll Chillers Critical Interlock

York YLAA Scroll Chiller Alarm B2: Compressor Motor Overload

Published: 2026-05-08

🔍 Symptoms Checklist

  • ⚠️ Specific compressor contactor trips on overload relay
  • ⚠️ Compressor motor draws >125% RLA before trip
  • ⚠️ Overload relay is hot to touch after trip
  • ⚠️ Alarm is manual reset — will not auto-restart

🛠️ OEM Replacement Parts

Part NameOEM Part NumberEst. Price
Compressor Overload Relay (Class 10) YK-OLR-010 $145
Compressor Contactor (3-Pole, 50A with Aux) YK-CONT50 $185
Run Capacitor Bank (set of 3, 60 μF each) YK-CAP-BANK3 $240

📋 Interactive Diagnostic Procedure

Click each step to expand detailed diagnostic instructions. Follow in sequence — each step builds on the previous one.

1 Measure Running Amps & Voltage Balance
Before assuming compressor failure, check the electrical supply. Measure each leg's running amps (all three should be within 10% of each other) and voltage (phase-to-phase, all three within 2% of each other). A 2% voltage imbalance can cause a 10-15% current imbalance. A voltage imbalance >3% requires correction at the building electrical panel before any further compressor diagnostics — the compressor is not the problem, the power supply is.
2 Verify Overload Relay Trip Class & Setting
York YLAA chillers use IEC Class 10 overload relays (trip within 10 seconds at 600% FLA). Verify the relay's amp setting matches the compressor nameplate RLA. A common field error: the overload relay was set to the wrong value after a previous compressor replacement (e.g., a 25-ton compressor installed where a 20-ton was, but the overload relay setting wasn't updated). Check and adjust the dial to match the installed compressor's RLA.
3 Megger Test the Compressor Motor Windings
Disconnect all compressor leads at the contactor and overload relay. Perform a 500V DC megger test: phase-to-phase and each phase-to-ground. Acceptable: >100 MΩ phase-to-ground, >50 MΩ phase-to-phase at 68°F. Borderline: 20-100 MΩ (motor can run but will have elevated leakage current that heats windings). Failed: <20 MΩ (replace compressor). For compressors in the borderline range, perform an acid test on the oil — high acid number indicates internal motor insulation breakdown into the oil.
4 Inspect Contactor for Single-Phasing
A burned contact on one pole of the 3-pole contactor creates a single-phase condition — the compressor motor tries to run on two phases, draws locked-rotor current, and trips the overload. Signs of single-phasing: that specific compressor contact is visibly burned/eroded compared to the other two, a humming sound from the compressor without rotation (before overload trip), and the overload trips within 2-5 seconds of contactor closure. Replace the contactor as a complete assembly — replacing individual contacts is unreliable.
Share this page Share on X

🔗 Related Error Codes — Scroll Chillers

Other diagnostic guides in the same equipment category. Common failure patterns often share root causes — cross-referencing speeds up diagnosis.

Scroll Chillers Critical Interlock

Carrier AquaSnap 30RAP Alarm 55: Low Suction Pressure — Freeze Protection

Alarm 55 on the Carrier AquaSnap 30RAP air-cooled scroll chiller indicates that the suction...

Scroll Chillers Critical Interlock

Trane CGAM Scroll Chiller Alarm LPC: Low Pressure Cutout — Circuit 1

The Low Pressure Cutout (LPC) alarm on Trane CGAM air-cooled scroll chillers protects the...

Scroll Chillers Critical Interlock

Daikin McQuay AGZ Chiller Alarm E1: Evaporator Flow Loss

Alarm E1 on the Daikin McQuay AGZ air-cooled scroll chiller indicates that the MicroTech III...

Scroll Chillers Critical Interlock

Carrier AquaSnap 30RAP Alarm 51: High Pressure Cutout — Condenser Issue

Alarm 51 on the Carrier AquaSnap 30RAP air-cooled scroll chiller is the high-pressure cutout for...

Scroll Chillers Critical Interlock

Trane CGAM Alarm HPC: High Pressure Cutout — Circuit Protective Trip

The High Pressure Cutout (HPC) alarm on Trane CGAM scroll chillers protects the compressor from...

Scroll Chillers Critical Interlock

York YLAA Scroll Chiller Alarm B5: Phase Loss / Phase Reversal Protection

Alarm B5 on the York YLAA scroll chiller is a system-wide lockout — the phase monitor relay has...

Scroll Chillers Critical Interlock

Daikin McQuay AGZ Alarm E3: Compressor Motor Overload — Thermal Trip

Alarm E3 on the Daikin McQuay AGZ scroll chiller indicates that a compressor's motor overload...

Scroll Chillers Warning (Defrost Mode)

Carrier AquaSnap 30RAP Alarm 52: Circuit Defrost — Freeze Prevention Active

Alarm 52 on the Carrier AquaSnap 30RAP indicates that the Pro-Dialog+ controller has activated...

⚡ Fault-Induced Energy Waste Estimator

When HVAC equipment runs with active error codes, it operates inefficiently and wastes electricity. Estimate the monthly cost of delaying repairs. All calculations run locally in your browser.

Copied!

References & Industry Standards

  • ASHRAE 15 — Safety Standard for Refrigeration Systems
  • ASHRAE 34 — Refrigerant Designation & Safety Classification
  • AHRI 550/590 — Water-Chilling & Heat Pump Packages
  • SMACNA — HVAC Duct Construction Standards
  • Manufacturer Service Manuals — Carrier, Trane, York, Daikin, Lennox