Scroll Chillers Critical Interlock

Daikin McQuay AGZ Alarm E3: Compressor Motor Overload — Thermal Trip

Published: 2026-04-29

🔍 Symptoms Checklist

  • ⚠️ Specific compressor trips on motor overload
  • ⚠️ Compressor contactor is energized but overload relay has tripped
  • ⚠️ Compressor housing is too hot to touch (>180°F)
  • ⚠️ Alarm does not auto-reset — requires manual reset at the overload relay

🛠️ OEM Replacement Parts

Part NameOEM Part NumberEst. Price
Compressor Overload Relay (Manual Reset, Class 10) DKN-OLR-010 $160
Compressor Contactor (3-Pole, 40A with 24V Coil) DKN-CONT-40 $140

📋 Interactive Diagnostic Procedure

Click each step to expand detailed diagnostic instructions. Follow in sequence — each step builds on the previous one.

1 Measure Compressor Running Amps vs. RLA
After resetting the overload relay, measure the compressor's running amps on all three phases after 10 minutes of operation at full load. All three phases should read within 10% of each other and below the compressor's rated load amps (RLA) on the nameplate. Amps at 120%+ RLA indicate a mechanical overload — the compressor is working against abnormally high head pressure, or the scroll set has internal mechanical drag from wear or liquid slugging damage.
2 Check Voltage Balance at Compressor Terminals
A 2% voltage imbalance causes approximately a 10% current imbalance, which can push one phase above the overload relay trip point while the other two phases read normal. Measure all three phase-to-phase voltages at the compressor contactor input. Calculate imbalance: (max deviation from average) ÷ average × 100. If imbalance exceeds 2%, the problem is in the building's electrical supply — not the chiller. Correct at the distribution panel (check for loose lugs, corroded connections, unbalanced loading across phases).
3 Inspect Overload Relay Trip Setting
The overload relay's current dial must match the installed compressor's RLA. If a compressor was replaced previously and the new compressor has a different RLA than the original, the overload relay setting may not have been updated. Compare the dial setting against the compressor nameplate RLA. A relay set to 15A when the compressor RLA is 18A will nuisance-trip. A relay set to 22A with a 18A compressor will not protect the motor.

🔗 Related Error Codes — Scroll Chillers

Other diagnostic guides in the same equipment category. Common failure patterns often share root causes — cross-referencing speeds up diagnosis.

Scroll Chillers Critical Interlock

Carrier AquaSnap 30RAP Alarm 55: Low Suction Pressure — Freeze Protection

Alarm 55 on the Carrier AquaSnap 30RAP air-cooled scroll chiller indicates that the suction...

Scroll Chillers Critical Interlock

Trane CGAM Scroll Chiller Alarm LPC: Low Pressure Cutout — Circuit 1

The Low Pressure Cutout (LPC) alarm on Trane CGAM air-cooled scroll chillers protects the...

Scroll Chillers Critical Interlock

York YLAA Scroll Chiller Alarm B2: Compressor Motor Overload

Alarm B2 on the York YLAA air-cooled scroll chiller indicates that a compressor motor overload...

Scroll Chillers Critical Interlock

Daikin McQuay AGZ Chiller Alarm E1: Evaporator Flow Loss

Alarm E1 on the Daikin McQuay AGZ air-cooled scroll chiller indicates that the MicroTech III...

Scroll Chillers Critical Interlock

Carrier AquaSnap 30RAP Alarm 51: High Pressure Cutout — Condenser Issue

Alarm 51 on the Carrier AquaSnap 30RAP air-cooled scroll chiller is the high-pressure cutout for...

Scroll Chillers Critical Interlock

Trane CGAM Alarm HPC: High Pressure Cutout — Circuit Protective Trip

The High Pressure Cutout (HPC) alarm on Trane CGAM scroll chillers protects the compressor from...

Scroll Chillers Critical Interlock

York YLAA Scroll Chiller Alarm B5: Phase Loss / Phase Reversal Protection

Alarm B5 on the York YLAA scroll chiller is a system-wide lockout — the phase monitor relay has...

Scroll Chillers Warning (Defrost Mode)

Carrier AquaSnap 30RAP Alarm 52: Circuit Defrost — Freeze Prevention Active

Alarm 52 on the Carrier AquaSnap 30RAP indicates that the Pro-Dialog+ controller has activated...

⚡ Fault-Induced Energy Waste Estimator

When HVAC equipment runs with active error codes, it operates inefficiently and wastes electricity. Estimate the monthly cost of delaying repairs. All calculations run locally in your browser.

Copied!

References & Industry Standards

  • ASHRAE 15 — Safety Standard for Refrigeration Systems
  • ASHRAE 34 — Refrigerant Designation & Safety Classification
  • AHRI 550/590 — Water-Chilling & Heat Pump Packages
  • SMACNA — HVAC Duct Construction Standards
  • Manufacturer Service Manuals — Carrier, Trane, York, Daikin, Lennox