Centrifugal Chillers Critical — Compressor Protection

Carrier 19XR Alarm 105: Low Evaporator Refrigerant Temperature Diagnosis

Published: 2026-07-24

🔍 Symptoms Checklist

  • ⚠️ Leaving chilled water temperature drops below 36°F (2.2°C) setpoint
  • ⚠️ Alarm 105 displayed on PIC II/III controller with manual reset required
  • ⚠️ Compressor unloads to minimum capacity then locks out if condition persists
  • ⚠️ Evaporator refrigerant saturation temperature below 33°F (0.5°C)

🛠️ OEM Replacement Parts

Part NameOEM Part NumberEst. Price
Evaporator Refrigerant Temperature Sensor 19XR-TEMP-011 $285
Leaving Chilled Water Temperature Sensor 19XR-TEMP-004 $220
Electronic Expansion Valve (EXV) Actuator 19XR-EXV-ACT $1,400

📋 Interactive Diagnostic Procedure

Click each step to expand detailed diagnostic instructions. Follow in sequence — each step builds on the previous one.

1 Verify Chilled Water Flow Rate
Alarm 105 is most commonly caused by insufficient chilled water flow through the evaporator. Check the differential pressure across the evaporator (should match the design delta-P, typically 10-15 ft head). If delta-P is low, investigate: pump operation (verify pump is running and impeller is intact), strainer blockage (open and inspect the Y-strainer), air in the system (bleed air vents at the highest points), or closed isolation valves in the chilled water loop. A flow switch proving circuit should also be verified — a stuck flow switch can cause the controller to falsely report low flow.
2 Check EXV (Electronic Expansion Valve) Operation
The EXV modulates refrigerant flow into the evaporator. If the EXV is stuck open or overfeeding, the evaporator pressure drops rapidly, causing the saturated refrigerant temperature to fall below the low-limit setpoint. Use the PIC controller service menu to command the EXV through its full range (0-100%). The valve should respond within 2-3 seconds. A sluggish or non-responsive EXV indicates actuator motor failure or debris in the valve port. If the EXV is operating correctly, verify the superheat setpoint — an artificially low superheat target will cause overfeeding.
3 Verify Building Load vs. Chiller Minimum Capacity
During shoulder seasons (spring/fall), building cooling load may fall below the chiller's minimum stable capacity (typically 10-20% of full load). The chiller cannot turn down low enough, causing the leaving water temperature to fall below setpoint. If this is the case, the solution is either a bypass valve that mixes supply and return water to maintain flow, or a buffer tank that adds thermal mass. Verify the chiller is not oversized for the current load condition by checking the actual cooling demand (BTU/hr) against the chiller's minimum capacity.
4 Inspect Refrigerant Charge Level
Low refrigerant charge can cause abnormally low evaporator temperatures because the reduced charge shifts the operating point. Check subcooling at the condenser outlet (should match the manufacturer's chart for the current operating conditions). If subcooling is low (typically <5°F), the system is undercharged. Use the Carrier pressure-temperature chart for R-134a to verify proper charge. Document any refrigerant added — repeated recharging indicates a leak that must be located and repaired.
Share this page Share on X

Frequently Asked Questions

Can I lower the Alarm 105 trip point to prevent nuisance trips during low-load operation?

No. The 33°F setpoint is calibrated to prevent evaporator tube freezing. Lowering it risks catastrophic freeze damage. Instead, address the root cause: install a chilled water bypass valve, add a buffer tank, or stage multiple chillers so that no single chiller operates below its minimum capacity.

How quickly does freeze damage occur if Alarm 105 is bypassed?

Evaporator tube freeze damage can occur within 60-120 seconds of the refrigerant temperature dropping below 32°F. The rate depends on the water flow rate and the temperature differential. This is why the controller does not allow a simple reset — the alarm requires investigation and root cause correction before restart.

🔗 Related Error Codes — Centrifugal Chillers

Other diagnostic guides in the same equipment category. Common failure patterns often share root causes — cross-referencing speeds up diagnosis.

Centrifugal Chillers Critical Interlock

Carrier 19DV Chiller Alarm 104: Centrifugal Compressor Surge Diagnosis

Alarm 104 on the Carrier 19DV centrifugal chiller indicates a compressor surge condition — a...

Centrifugal Chillers Critical Interlock

York YK Chiller Alarm: Compressor Surge & High Lift Protection

The York YK centrifugal chiller features an advanced surge protection algorithm that monitors...

Centrifugal Chillers Critical Interlock

Daikin WMC Chiller Alarm E3: Motor Overcurrent & VFD Fault

Daikin WMC chillers use oil-free magnetic bearing centrifugal compressors with integrated...

Centrifugal Chillers Warning (Reduced Capacity)

Trane CVHE Chiller Alarm 8D: Low Evaporator Refrigerant Temperature

Alarm 8D on the Trane CVHE centrifugal chiller indicates that the leaving evaporator water...

Centrifugal Chillers Critical Interlock

Carrier 19DV Alarm 102: Low Oil Pressure — Compressor Lubrication Failure

Alarm 102 on the Carrier 19DV centrifugal chiller indicates that the compressor's lubrication...

Centrifugal Chillers Warning (Reduced Capacity)

York YK Chiller Alarm: High Oil Temperature — Oil Cooler Performance

The York YK centrifugal chiller monitors oil sump temperature via an RTD sensor in the oil...

Centrifugal Chillers Critical Interlock

Trane CVHE Alarm 8A: High Condenser Pressure — Heat Rejection Failure

Alarm 8A on the Trane CVHE centrifugal chiller indicates that the condenser pressure has...

Centrifugal Chillers Critical Interlock

Carrier 19XR Alarm 125: Motor Bearing High Temperature — Hermetic...

Alarm 125 on the Carrier 19XR hermetic centrifugal chiller monitors the motor bearing...

⚡ Fault-Induced Energy Waste Estimator

When HVAC equipment runs with active error codes, it operates inefficiently and wastes electricity. Estimate the monthly cost of delaying repairs. All calculations run locally in your browser.

Copied!

References & Industry Standards

  • ASHRAE 15 — Safety Standard for Refrigeration Systems
  • ASHRAE 34 — Refrigerant Designation & Safety Classification
  • AHRI 550/590 — Water-Chilling & Heat Pump Packages
  • SMACNA — HVAC Duct Construction Standards
  • Manufacturer Service Manuals — Carrier, Trane, York, Daikin, Lennox

Centrifugal Chiller Diagnostics — Engineering Reference

Centrifugal chillers are the workhorses of large commercial cooling — hospitals, data centers, university campuses. They use centrifugal force to compress refrigerant vapor, achieving capacities from 200 to 10,000+ tons. Fault diagnosis requires understanding the interplay between condenser water temperature, evaporator approach, oil pressure, and surge dynamics.

Applicable Standards

ASHRAE 15 (Safety), AHRI 550/590 (Performance), ASME BPVC Section VIII (Pressure Vessels)

Common Failure Modes

Compressor surge at low-load conditions. Oil loss due to refrigerant migration. Tube fouling reducing heat transfer efficiency. VFD harmonics causing motor bearing failure. Non-condensables raising head pressure.

Technician's Field Note

Before condemning a centrifugal compressor for surge, verify condenser water temperature and flow rate — the #1 cause of surge is high condenser water temperature from a fouled cooling tower or a failed tower fan motor, not a compressor fault.